Bi-French diaphragm pressure transmitterClick on the picture to zoom in.
PRODUCT SPECIFICATIONS
PRETRAN-DM-250
Bi-French diaphragm pressure transmitter
Bi-French diaphragm pressure transmitter, bi-French remote, closed container applicable
01
Classification: bi-French diaphragm pressure transducer
02
Check configuration based on field work
TECHNICAL SPECIFICATIONS
Technical specifications
Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.
View selection tables ↓| Model | PRETRAN-DM-250 |
|---|---|
| Measurement principle | Monocrystalline silicon / diffused silicon differential pressure core + double diaphragm seal Capillary remote |
| Measurement type | Differential pressure (D) / Sealed container level (L) / Interface (I) / Density (old) |
| Measurement range | 0–1kPa to 0–6MPa (turndown ratio 50:1 Adjustable) |
| Accuracy class | ±0.25% / ±0.5% (Optional) |
| Maximum static pressure | 2.5MPa / 5MPa / 10MPa (Optional) |
| Overload capacity | 3 Range |
| Output signal | 4–20mA (DC) two-wire / 4–20mA+HART / RS485 (MODBUS) Optional |
| Power supply | 12–36VDC (standard 24VDC), Two-wire Loop power |
| Load capacity | (Supply voltage − 12 V) / 0.02 A, up to 1.2 kΩ |
| Diaphragm material | 316L (standard), Hastelloy C276, tantalum Ta (Optional) |
| Diaphragm seal body / flange | 316 stainless steel DN50–DN100 flange (PN1.0–4.0), flat/ Insertion |
| Capillary | 2m (standard), 3/5/10/15m optional, φ3.2 Stainless steel weaving Mineral-insulated |
| Fill fluid | Silicone oil (standard) / low-temperature silicone oil / food-grade glycerin |
| Display type | 3½ bit LED / 4 LCD (Optional), key full of zero points |
| Damping time | 0–15s Configurable |
| Stability | ±0.2% /year |
| Process medium temperature | -40–+120℃ (silicone oil) / -80–+200℃ (Low-temperature silicone oil) |
| Ambient temperature | -40–+85℃ (Capillary full-time) |
| Ingress and explosion protection | IP66/67; Ex d II C T6 Gb / Ex ia II C T4 Ga (Optional) |
| Electrical connection | Hirschmann Hersmann connection / M20×1.5 cable sealed |
| Applicable standards | GB/T 17614 / IEC 61010 / JB/T 8611 (Diaphragm Seal) |
| Suitable media | Closed packaging Level / Interface / Density, measurement of high viscosity, crystallization, condensation, strong corrosive medium Differential pressure |
Product selection
PRETRAN-DM-250| Code | Measurement type |
|---|---|
| T1 | Differential pressure (D) |
| T2 | Closed container level (L) |
| T3 | Interface/density (I /old) |
| Code | Range options (kPa) |
|---|---|
| R1 | 0~1kPa~0~10kPa |
| R2 | 0~10kPa~0~100kPa |
| R3 | 0~100kPa~0~6000kPa |
| Code | Accuracy class |
|---|---|
| E1 | ±0.5%FS |
| E2 | ±0.25%FS |
| Code | Maximum static pressure |
|---|---|
| P1 | 2.5MPa |
| P2 | 5MPa |
| P3 | 10MPa |
| Code | Output signal |
|---|---|
| O1 | 4–20mA Two-wire (Standard) |
| O2 | 4~20mA + HART |
| O3 | RS485(MODBUS-RTU) |
| Code | Diaphragm material |
|---|---|
| M1 | 316L Stainless steel |
| M2 | Hastelloy C276 |
| M3 | Tantalum Ta (strong corrosive) |
| Code | Diaphragm seal body type |
|---|---|
| F1 | Paste Flange (Standard) |
| F2 | Insertion Flange (high temperature/crystal) |
| Code | Nominal flange size / pressure rating |
|---|---|
| N1 | DN50 PN1.0 / PN2.0 |
| N2 | DN80 PN1.0~PN4.0 |
| N3 | DN100 PN1.0~PN4.0 |
| Code | Capillary length |
|---|---|
| C1 | 2m (Standard) |
| C2 | 3m / 5m |
| C3 | 10m / 15m (Specify when ordering) |
| Code | Fill fluid |
|---|---|
| Y1 | Silicone oil (Standard) |
| Y2 | Low-temperature silicone oil (-80℃) |
| Y3 | Food class Glycerin |
| Code | Display type |
|---|---|
| L1 | No display (Standard) |
| L2 | 3½ bit LED digit Display |
| L3 | 4 bit LCD display + Key change |
| Code | Explosion protection marking |
|---|---|
| X1 | Non-Ex |
| X2 | Flameproof Ex d II C T6 Gb |
| X3 | Intrinsically safe Ex ia II C T4 Ga |
Confirm specifications and ordering options
Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.
Contact us