Thermal dolls for temperature measurement at the station

Operating principle

Thermal dolls for temperature measurement at the station.

The temperature component uses the K/N/E/J/T/S/R/B equivalent to measure the temperature based on the Seebeck thermoelectric effect. Two different metal conductors A and B form closed circuits, and if the temperature of the two points is different (T heat ⁇ T0 cold end), the heat power EAB: EAB (T, T0) = ⁇ [T0 ⁇ T] (SA - SB) dT where SA, SB are the Seck factor (V/K) for both metals. Thermal power is only related to materials, temperature and not to the geometric dimensions of the conductor. The power-temperature relationship of the usual fractional number at the station follows the IEC 60584 standard, EAB(T) checklist available, detected

  1. 01

    1 The law of the uniform conductor . The temperature of the single equal conductor is not thermally high.

  2. 02

    2 The intermediate conductor's law ..access to the third conductor in return, with the same temperature at both ends, and thermal power remaining constant.

  3. 03

    3 The law of the intermediate temperature = EAB (T, T0) + EAB (Tn, T0)

  4. 04

    4 . Reference EAB (T, T0) = EAC (T, T0) - EBC (T, T0)

Thermal voltage support for temperature measurement at stations

Provide survey missions, media and installation conditions and obtain product configuration advice.

Contact us
· Technical note

TECHNOLOGY & APPLICATION

Understand the principles, the exact selection.

From measurement principles to field applications, the technical characteristics and selection features of thermoelectric dolls for temperature measurement purposes at power stations are known.

01

TECHNICAL GUIDE

Overview

(Power Plan Service Thermocouple, WR / WRP series) is an industrial thermoelectric thermome sensor designed for super-high-temperature high-voltage vapour and flue gas temperature monitoring in power plants, nuclear power plants and large industrial boilers. Its core idea is to "separate high-pressure vapours and flue gases with high-intensity heat tubes, and accurately measure temperature with thermal effect of the Selbeck”, to isolate the thermometroph temperature from high-temperature high-pressure media in a completely safe manner, by means of targeted designs such as the incremental (step) heat casings, Inconel 600 / GH3030 protection tubes, vibration support, and high-pressure seals, which ensure both temperature accuracy and mechanical reliability in the case of boilers when they are activated, vibrations, and pressure fluctuations.

It is one of the most critical and stringent temperature measurement programmes in the generator unit thermometry system. Thermal voltage is higher than thermal resistance (K type 1300°C, S/R type 1600°C), faster response (naked < 1 s), and more resilient, especially for the main station ' s vapour export, reheater, flue gas, combustionr, etc. The station boiler can have a temperature of 540 ~620°C, pressure 10 ~ 25 MPa, current speed 30 ~ 100 m/s, and a strong mechanical vibration caused by the combustion pulse. The normal assembly thermoelectric doll or charlatan is directly exposed to the above conditions and the protective tube is either crushed, broken or disabled by high pressure. Thus, the temperature measurement of the power station must be based on a plant-type thermoelectric doll accompanied by a dedicated heat tube, which is typically structured as a gradual (step) heat tube, a whole-made heat tube, a welding tube, a piping tube, etc.

Main technical characteristics

General description · Serial number / CharacteristicsCross-reference
Serial numberCharacteristics
1High-intensity heat tube: Gradual / Whole exercise / Welding heat tube to meet ASME PTC 19.3 strength accounting
2Maximum temperature measurements height: K type 0~1300 °C, S/R type 0~1600 °C, high temperature stations adapted to power stations
3Respond speed: naked thermovolts < 1 s; protective tube 5~20 s, 3~6 times faster than thermal resistance
4Protection tube high temperature: Inconel 600 / GH3030 / GH3044 / Harsh C-276 / 1 Cr18Ni9Ti
5Vibration protection structure: inner line spring / anti-earthquake support / anti-vibration gasket / incremental heat tube
6High-pressure-proof structure: metal seals metal cones / entanglement pads / lens pads / strong seals
7Process connections: high pressure flange HG/T 20615 / ANSI 600#~2500 / Welding
8Full symmetry: K/N, E/J, T, S/R/B, eight main symmetry, covered -40 ~ +1600 ℃
9Site is complete: Thermostat / Reheater / Frozen / Incendiary / Main steam / Autowheel / One-way scene
10Life: reasonable selection 3-6 years, matching the power plant overhaul cycle
02

MEASUREMENT PRINCIPLE

Operating principle

2.1 Thermal electrical effects of Sebek

The temperature component uses the K/N/E/J/T/S/R/B-symmetric thermo-temperature pairs, which are measured on the basis of Seebeck 's thermoelectric effects. Two different metal conductors, A and B

When forming a closed circuit, if the temperature of the two points is different (T hot end po) T0 Cold end, heat power in the circuit EAB:EAB (T), T0 ) = ∫[ T0 ⁇ T] (SA - SB) dT where SA, SB are the Seckbeck coefficient (V/K) for two metals. Thermal power is only related to materials, temperature and not to the geometric dimensions of the conductor. The power-temperature relationship of the station ' s commonly used fractional number follows the IEC 60584 standard, the EAB(T) checklist is available and the EAB countercheck can be detected to obtain temperature T.

8 Large Basic Law of the Station.

2.2 The cold-end compensation rationale

Thermal electromechanical table is based on cold-end 0℃, but the actual cold-end is usually at ambient temperature (-20 ~ +60)

The cold-end compensation method is common:

2.3 Power station heat tube resistance to high pressure

The core of the thermomechanical dolls for temperature measurement at the station is the thermowell design. Thermal tubes are exposed to high temperature, high pressure vapour media.

, the requirements for accounting for strength of ASME PTC 19.3 Themoules or ASME B16.5 / B31.1 must be met:

2.4 Visibility protection

The station boiler produces strong vortex-inducated vibration (Vortex-induced Vibration) due to combustion pulses, water fluctuations and flow incentives for the soda mixture. G = burn frequency of the boiler / ratio of the inherent frequency of the protective tube. When G approaches 1

The resonance occurs at a time when the protection tube is broken in a short time.

Inline spring support

Add springs to the protective tube to support the temperature and spread the vibration stress;

Welding or French Installation

Avoiding the looseness of screwdriver connections;

Shorten depth of insertion

(b) Minimize the length of the arm while ensuring a representative temperature measure;

Five, shielding position.

The spot avoids high-flow areas such as piped circuits, valves, and throttles.

2.5 Thermal work flow at the power station

Measurement formulaClick to see the big picture
EAB(T, T0) = ∫[T0→T] (SA − SB) · dT
The principle of work . Serial number / Basic lawCross-reference
Serial numberBasic lawsAnnotations
1Law of the Mean ConsortSingle-equitable conductor with no heat or power at both ends
2The Law of the Intermediate ControlsAccess to the third conductor on the circuit, with the same temperature at both ends, and no heat or power.
3The law of the middle temperature.EAB(T, T0) = EAB(T, Tn) + EAB(Tn, T0)
4Reference to the laws of electrodesEAB(T, T0) = EAC(T, T0) − EBC(T, T0)
5Law of ConnectorWhen thermal circuits connect to the main line, the circuits are only subject to the temperature of both ends.
6Temperature-Electro-More ModemThermal power-temperature relationship is monotonous for each fractional sign, which can be directly checked
7The laws of polarity.The greater the temperature difference between the heat and the cold, the greater the heat power, and the heat is positive E > 0
8Alternative LawThermal power of two different materials, C and D, equals the difference between the heat and the reference electrodes.
The principle of work . Serial number / Compensation LawCross-reference
Serial numberCompensation ActRationalePrecision
1Ice bathing.Cold end 0 °C ice water mixture, reference electrodesMaximum ± 0.1 °C (laboratory)
2Checklist amendmentsMeasure cold end temperature, reverse correction from the fraction tablemedium ±1~2 °C, power station manual
3Compensatory route methodExtend cold end to instrument with a cheap compensatory guide matching the thermoelectric poleMedium ± 1 °C, Mainstream of power station
4Cold-end temperature compensation methodIntegrated Bridge Compensator (AD594/MAX31855, etc.)High ± 0.5 °C, station smart transporter mainstream
Modus operandi . Level / Publicly referred to pressure (MPa)Cross-reference
LevelPublicly known pressure (MPa)Typical applicationsHot tubing form
Low Pressure PN ≤ 2.5≤ 2.5Low pressure steam, water, water back.Straight pipe / screwdriver connection
Medium pressure PN 4.0-104.0~10Water from the middle pressurized boiler, excessive heat steamStraight tube / Welding / Gradient
High pressure PN 10-2510~25High pressure boiler overheater, reheaterGradual/ step/ whole exercise
Super-high pressure PN ≥ 25≥ 25Supercritical, nuclear conventional.Whole exercise / stacking / segments expanding
Motion of work . Step / ActionCross-reference
StepsActions
①Overheated steam / flue gas / heat for water temperature ⁇ heat for tube heat ⁇ inner protective tube ⁇ heat for the voltage
②The Sebek effect, thermal and cold temperature differentials produce heat EAB (T, T0)
③Compensatory conduits extend EAB to the side of the cabinet (cool end stabilized at 0~60°C)
④Transmitters cold-end temperature reimbursement + linear 4-20 MA / Hart / bus
⑤Signal sent to DCS / DAH / Coordinated Control Display, Alert, Record, AutoControl
⑥Participation in boiler combustion, water supply, temperature-reducing spray, heat-excavation chain control
⑦Excess / Open / Short-Range & Zoom to malfunction (≤ 3.6 mA or ≥ 21 mA)
⑧Thermal electromechanical plant drift or heat tube failure
03

PRODUCT STRUCTURE

Product structure

3.1 Main structural components

3.2 Thermal tube structure forms (5 classes)

3.3 Measurement end-end structure forms (4 classes)

3.4 Structure forms

Thermal Puppet Temperature (Measure End)

Functional description: Thermal power core of Sebek, which is composed of two different metal welds of the velvet material/specifications commonly used: K (KP/KN), N (NP/NN), E, J, T, S/R/B

Internal protection tube

Functional description: Thermal electromechanical end protection and heat conductor Usual material/specifiers: Inconel 600 / GH3030 / GH3044 / Harsh C-276 / 1 Cr18Ni9Ti / ceramic

Therm owell

Functional description: Pressure, isolation, high temperature, high pressure medium, key component for temperature measurement at the power station Common material/specification: 12Cr1MoV / 15CrMo / 1Cr18Ni9Ti /F22 /F91 / Stack Inconel 600 / Whole exercise

Inline spring (invigoration)

Functional description: Supporting temperature, dispersive vibration stress Usage material/specify: Inconel 600 / 316L spring

Insulation (porcelain / china pole)

Functional description: separation of vegetable wire, avoiding short circuits Common mass/specification: Aluminium oxide / ceramic skeleton / boete insulation

Compensatory guide

Functional description: Thermal power extends to the side of the cabinet and compensates for cold-end temperature Usual materials/specifies: K type KX / N type NX / E Type EX / S/ R type SC/RC / bot-insulated high temperature line

Cold-end seal / Substrate

Functional description: tail seal, connector end. Common material/specifier: ceramic glue / epoxy / stainless steel base.

Connecting box caps

Functional description: protection line end, easy to maintain Usual materials/specifiers: Aluminium alloy / stainless steel / IP65 ~IP68 / Detonation Exd / Exia

Connector End

Functional description: Compensated guide lines and signal cables

Process connection

Functional description: Installation in heat perheater / reheater / flueque Usage Usage/Specific: High Pressure Frank HG/T 20615 PN16 ~PN32 / ANSI 600#~2500 / Welding

Transmitters (optional)

Functional description: Integrated signal conversion + cold-end compensation Usual material/specification: 4-20 ma + Hart / MODBUS / PROFIBUS-PA / Foundation Fieldbus

Deck / Warning

Functional description: Identified fraction, point, temperature, pressure, length Common material/specify: stainless steel / aluminium alloy engraving

Form

Name of component: Structural characteristics Functional description: Typical application Usual material/specify: pressure level

Straight line

Name of component: Conservatory tube integrated with thermal tube straight line, Equivalent processing Function description: Low pressure vapour / water supply / flue gas Usual material/specifier: ≤ 2.5 MPa

Gradual expansion (stepping)

Name of component: root thickened, increase in inherent frequency, oscillation Description of function: high pressure over thermal steam, reheated steam Usage/Specific: 10~25 MPa

Whole exercise.

Name of component: Total exercise, high intensity, long life Function description: supercritical mass main vapour Usage Usage/Specific: ≥ 25 MPa

Welding

Structural characteristics: Carbon steel matrix + Inconel welding layer, machine strength + corruption resistance double advantage Typical application: HT, reheater Pressure level: 10~25 MPa

Welding / screwdriver

Structural characteristics: Direct welding or screwdrivers connected to the tube wall Typical application: Saver of coal / Water / Pressurized steam level: ≤ 10 MPa

Form

Structural characteristics: Structural characteristics Typical applications: Typical applications Pressure levels:

Headbrow (shell-style)

Structural characteristics: Thermal direct welding at the end of the protective tube, responding most quickly.

Insulation

Structural characteristics: Thermal welding points are insulated with magnesium oxide and protective tube, resistant to interference, strong, typical applications: main steam, reheater (mainstream) of the power plant, pressure level:

Shell type

Structural characteristics: Welding point heat and tube connection, high mechanical strength Typical application: high pressure, high vibration point Pressure level:

Pane / Head-out

Structural characteristics: Top-exposed, faster response. Typical application: Frozen temperature rapid response. Pressure level:

Form

Structural characteristics: Structural characteristics Typical applications: Typical applications Pressure levels:

Welding

Structural characteristics: Thermal tube is welded directly into the outer wall of the pipe Typical application: high pressure overheater / main steam pressure level:

French

Structural characteristics: Connected through high pressure flange (HG/T 20615 / ANSI 600#~2500#) Typical application: Export of heater / reheater import/export Pressure level:

Thread

Structural characteristics: Twisted equipment directly through NPT/ G screws

Card

Structural characteristics: Stabilizing through screwdrivers to facilitate the Depths Typical application: low pressure to water / test circuit

Active French

Structural characteristics: Frank + Sealed rings can be adjusted along the tube. Typical applications: frequent on-site / multipoint temperature measurement pressure level:

04

TECHNICAL GUIDE

Advantages and disadvantages

Product advantages

High temperature limit

Specific: K 1300 °C, S/R 1600 °C, B 1700 °C, far over thermal resistance + 650 °C

Respond fast.

Specific: Naked Thermal Puppet < 1 s; protective tube type 5~20 s, 3~6 times faster than thermal electrical resistance

High pressure high intensity

Specific: Gradual / Whole exercise heat tube meets ASME PTC 19.3, 10~25 MPa safely run

We're good at protection.

Specific: Gradual + inner liner spring support, inherent frequency avoided burn pulse resonance

All the points.

Specification: K/N/E/J/T/S/R/B 8 main semi-dimensional numbers, covered -40 ~ +1700 ℃

Simple and reliable structure

Specific: Two metal filament structures, passive devices, long-term stability at the power station level

Stations are complete.

Specific: Thermostat / Reheater / Frozen / Incendiary / Main steam / Gas Wheels Panorama

Integration with Transmitters

Specific: Integrated temperature adapter, home-borne cold end compensation + linear

Disadvantages and use restrictions

Temperature accuracy below heat and electricity.

Response: ±1.5 ℃ or ±0.4% t, S/ R ±1.0 ℃ or ±0.4% t, which is different from Pt100 ±0.15 ℃; high-precision temperature selection heat and electrical resistance

Cold end compensation dependency line

Response: Compensation of a back-linking or model error will result in tens of degrees of C error; the correct fractional compensation guide KX / NX / EX / SC/RC must be accompanied

Insert Depth Large, Install Space High

Response: Overheated vapour temperature measurement requires the insertion of a pipe 1/3 diameter, often 600 ~ 1200 mm; space restricted positions need to be fitted with a shorter or elbow structure

The heat tube weighs a lot.

Response: The whole-body exercise of thermal tube can be up to 20 ~ 60 kg in single units, with a special lifting tool for installation and repair

Vibration failure risk

Response: Turboflow Vibration Protection Pipes when they are not properly selected or installed; the inherent frequency is to be accounted for by ASME PTC 19.3

Higher prices

Response: Overall exercise + Inconel Welding Suite price is 5-10 times more than normal

Floating and ageing

Response: gamma dichotomy, drifting; verification or replacement during major repairs

05

APPLICATIONS

Application area

Temperature measurements used extensively at key stations of the following power stations

The boiler overheater exit

Application area: High temperature overheat 540 ~ 620 °C / 10 ~ 25 MPa / 30 ~ 80 m/s Typical medium: overall exercise + Inconel 600 stacks / K or N Recommended heat tube/protector/ fraction:

The boiler reheater is imported and exported.

Application area: Reheated vapour 540 ~ 610 °C / 4 ~ 10 MPa typical medium: Gradual + Inconel 600 / K Recommended heat tube/protector/spectrum:

Screen Overheater

Application area: High temperature high pressure overheat 450 ~ 620 °C Typical medium: Gradual + 1Cr18Ni9Ti / Inconel 600 / K Recommended heat tube/protector/spectrum:

Top-level heater

Application area: Main steam export 540 ~ 620 °C / 17 ~ 25 MPa typical medium: total exercise + stacking Inconel 600 / K or N

Frozen side temperature

Application area: Boiler / Saved coals after / Air preheater front fumes 200 ~ 1100 °C Typical medium: straight tube + Happiness C-276/Inconel 600 / GH3030 / K or S Recommended heat tube/protector/specific point:

Burner temperature

Application area: Fireplace of the furnace area 1100 ~ 1700 °C Typical medium: high temperature + cooling tube / B or S-precious metal Recommended heat tube/protector/spectrum:

Temperature after cooling the spray

Application area: Thermal excess steam 400 ~ 540 °C typical medium: Gradual + Inconel 600 / K Recommended heat tube/protector/specific number:

Heat wall temperature

Application area: Perheating tube wall monitoring 500~620 °C Typical medium: Pumps / Puppets / K Recommended heat tube/protector/spectrum:

The reheating wall temperature

Application area: Reheater tube wall monitoring 500 ~ 600 °C Typical medium: Pumps / Puppets / K Recommended heat tube/protector/spectrum:

Nuclear power is a one-way road.

Application area: Reactor coolant 280~330 °C / 15 MPa typical medium: straight tube + 1Cr18Ni9Ti/K, special nuclear stage certification Recommended heat tube/protector/drive:

Nuclear Power Conventional Island

Area of application: soda separators, 2nd circuit, main steam 280 ~ 320 ℃ Typical medium: Gradual + 1 Cr18Ni9Ti/ F22/ K RECOMMENDED HEALTH PHILE / PROTECT / SPECIFIC No.:

Cylinder temperature / bearing

Application area: Outer walls of the cylinder 300 ~ 500 °C/ bearing 60 ~ 90 °C Typical medium: straight tube / / / / K or E

Thermal recovery boiler.

Application area: excess heat boiler steam 400 ~ 500 °C Typical medium: Gradual + 1 Cr18 Ni9Ti / Inconel 600 / K Recommended heat tube/protector/spectitude:

Waste generation / biomass

Application area: excessive heat steam 400 ~ 480 ℃ The smoke is corrupted. C-276 / Inconel 600 / K Type Recommended heat tube/protector/spectrum:

06

TECHNICAL SPECIFICATIONS

Technical Parameter Table

6.1 Overall technical indicators

6.2 Comparison of technical parameters for the fractional sign

6.3 Control Tables for temperature resistance of heat-plumbing materials

6.4 Control Tables for protection of tube content

  1. 01

    Naming rules for thermometeoroid models for thermal measuring stations of selected forms (cf. JB/T8623+DL/T)

5210)

W (temperature instrumentation) R (thermal voltage) K (several K/N/E/J/S/R/B)x (protective tube)-□ (heat tube form direct/scaling/ exercise)-□ (publicly called PN16 ~PN32)-□ (process connection Frank/welding/snailing)-□ (insert depth L)-□ (explosive/output)

7.1 Type by Point Type

7.2 Type in the form of a hot tubing

7.3 Type by fraction

7.4 Select by Process Connect

7.5 Type by Output

  1. 01

    Selection Guide

8.1 Selection Processes

the selection shall be determined in the following order:

8.2 Select type of heat resistance compared to thermal resistance for temperature measurement at the power station

8.3 Decision Tree for the Key Site at Power Station

1 Main steam export / upper-stage overheater (Pesostatic) > 600 ℃ / 25 MPa ) Part of the exercise + F91 Base + Inconel 600 Welding tubes + K or N;

2 Reheater Import/Export ( 540 ℃ / 4 ~ 6 MPa ) Gradual expansion + Inconel 600 Protection tube. + 1 Cr18Ni9Ti heat tube + K;

3 Screen Overheater ( 450 ~ 580 ℃ / 15 MPa ) Gradual expansion + Inconel 600 + 1 Cr18Ni9Ti heat tube + K;

4. High pressure to water ( 290 ℃ / 25 MPa Gradual expansion + 1 Cr18Ni9Ti heat tube + 1 Cr18Ni9Ti protection tube + K;

5 Packet Temperature 360 ℃ / 18 MPa Direct liner + 1 Cr18Ni9Ti/ Welding+K;

6 Province of coal-fired imports and exports (in thousands of United States dollars) 150 ~ 350 ℃ / 4 MPa > Direct tube / Welding + 1 Cr18Ni9Ti+K or E;

7 Air preheaters 30 ~ 200 ℃ / 0.1 MPa Direct liner + 316 L+K or T;

8 Frozen side() 200 ~ 1100 ℃ / 0.1 MPa ) + Hax C-276 / Inconel 600 / GH3030 + K or S;

⑨ Burner flame (1100–1700 °C / 0.1 MPa): use a high-temperature assembly with a cooling jacket, ceramic protection tube, and a noble-metal Type B or Type S thermocouple.

10 After cooling spray ( 400 ~ 540 ℃ / 15 MPa ) Gradual expansion + Inconel 600 +K type;

Supercritical main steam (U.S.C.) > 620 ℃ / ≥ 25 MPa ) Part of the exercise + TP347H Welding Inconel 600 +N (prevent gamma dialysis);

Nuclear power one loop (320 °C / 15 MPa) + 1 Cr18 Ni9Ti + K + Nuclear Level Certification.

8.4 Attention to thermometeorized plant installation for temperature measurement

Inserting depths, as required by the process, overheated vapour temperature measurement into the pipe 1 / 3 diameter to avoid heat error;

2 Point position should be avoided by downwards of piped bends, valves, throttles. 5 High current area within D;

3 Welding requirements for the root of the extended hot tubing 100% (b) Radioprospecting + infiltration detection;

The French connection should use gaskets (soft graphite/tangular pad/metal ring pad) matching the medium, and be evenly secured to avoid bias;

Welding in high temperature high pressure areas to avoid loose threading;

6 Explosive-proof wire boxes (Exd II) must be used in blast-proof settings BT4 / Exia II CT6 and secure seals;

7 Operator boxes shall be sealed to protect against tide. IP65 above), wet environment selection IP67/IP68 ;

Compensatory guides must match the thermopolymers (K ⁇ KX, N ⁇ NX, S ⁇ SC, R ⁇ RC) and be non-reversible;

The lead line penetrator should use blast-resistant or metal hoses to avoid mechanical damage;

The protective tube shall be thoroughly inspected during major repairs, with a view to the appearance, thickness, welding and, if necessary, the in situ or sample verification of the thermoelectric dolls;

(b) The prohibition on shipping when vibration accounting is not passed and the replacement of incremental or additional anti-vibration support is required;

When K-type thermoelectric dolls are used over a long period of 800°C, care is taken to balance the gamma phase and it is recommended that the overhaul or replacement be undertaken.

8.5 Maintenance element

— End of document —

Technical Table of Parameters . Parameter Item / Parameter ValueCross-reference
Parameter ItemParameter Value
Product implementation standardsIEC 60584 / IEC 61515 / ASME PTC 19.3 / JB/T 8623 / JB/T 9238 / GB/T 18404 / DL/T 5210
Temperature Component TypeK, N, E, J, R, S, B thermo-pants against silk (IEC 60584).
Accuracy classK/ N type ±1.5 ℃ or ±0.4% t (extract large); S / R type ±1.0 ℃ or ±0.4% t;B type ±1.5 ℃ or ±0.5% t
Temperature rangeK/N -40~+1300 ℃;E -40~+900 ℃;J -40~+750 ℃;T -40~+350 ℃;S/R 0~+1600 ℃;B 0~+1700 ℃
Protection tube materialInconel 600 / GH3030/ GH3044 / Harsh C-276/ 1Cr18Ni9Ti/ ceramic / 310S
Hot tubing material12Cr1MoV / 15CrMo / 1Cr18Ni9Ti / F22 / F91 / TP304H / TP316H / TP347H / Stack Inconel 600 / Whole exercise
Exterior Specification⁇ 16 / ⁇ 20 / ⁇ 22 / ⁇ 25 mm mainstream, which can be expanded to 30~50 root
Insertion depth L200 / 300 / 400 / 500 / 600 / 800 / 1000 / 1200 / 1500 / 2000 mm or custom
Process connectionHG/T 20615 PN 16 ~ PN 32 / ANSI 600 ~ 2500 #; Welding; screwdriver NPT/G / M
Response Time t0.5nudity K < 1 s; protective tube ⁇ 16 about 8~20 s; ⁇ 25 about 15~40 s
Operating pressureConstant pressure / 2.5 / 4.0 / 6.4 / 10 / 16 / 20 / 25 / 32 MPa (at Frank level)
Cold junction compensationCompensatory guide extension to the side of the cabinet + Transmitter smart compensation (AD594/MAX31855).
Ingress protectionIP65 / IP67 / IP68 (Accompanying connection box)
Explosion protection markingExd II BT4 / Exia II CT6 (by region)
Line ModeSecond / Third / Four-line; Thermal dolls general nd line (polarity distinction)
Output signalmV / 4-20 mA / Hart / MODBUS / PROFIBUS-PA / Foundation Fieldbus
Use temperature (wirebox)40~+85 ℃
Relative Humidity5% ~ 95% RH, no condensation
Storage temperature40 ~ +85 ℃, dry and ventilated
Vibration resistance≥ 60 Hz; G = boiler frequency / inherent frequency < 0.8
Life expectancy3 ~ 6 years (compatible with major power plant repair cycle)
Weight (reference)Φ 25 × 1000 The whole thing. 25 kg;Φ 16 × 500 Gradual expansion of the convention 6 kg
Technical parameter table . . / MaterialsCross-reference
Sensor typeMaterialsTemperature range100 °C power (mV)1000 °C power (mV)Apply scene
KKP (Nicychromium) / KN (Simple Nickel)40~+1300 ℃4.09641.276Main station / Overheated Vapour / Fung
NNP(NiCrSi) / NN(NiSi)40~+1300 ℃2.77436.246K Upgrade / Resist gamma Division / High Temperature Long-Term Stability
EEP (NiChrome) / EN (Cronium Nickel)40~+900 ℃6.31976.873Medium-Leo Temperature / Vapour / Water / Thermal Loss
JJP (iron) / JN (copper nickel)40~+750 ℃5.26957.953Media neutral / Revert atmosphere
TTP (Cronic) / TN (Cronic Nickel)40~+350 ℃4.279—Low temperature / Cold end compensation guide
SSP( ⁇ 10) / SN (Purple)0~+1600 ℃0.6469.587Precious metal / high temperature / burner / standard
RRP(13) / RN(Purple)0~+1600 ℃0.64710.503Precious metal/ high temperature/ similar to S
BBP(30) / BN(6)0~+1700 ℃0.033—Super-high / burner / glass industry
Serial numberHot tubing materialApply the pointTemperature limitPressure rating
112Cr1MoVHigh pressure to water / medium pressure over thermal steam+580 ℃≤ 16 MPa
215CrMoHigh pressure overheater / reheater+560 ℃≤ 25 MPa
31Cr18Ni9Ti (321)Thermostan export / reheater / water+650 ℃≤ 25 MPa
4F22 (12Cr2Mo1)High pressure to water / main steam+595 ℃≤ 25 MPa
5F91 (T91 / P91)Supercritical main steam.+650 ℃≥ 25 MPa
6TP304H / TP316HHeats / Reheaters+700 ℃≤ 25 MPa
7TP347HSuper-critical overheat exit.+700 ℃≥ 25 MPa
8Whole exercise + stacks of Inconel 600Supercritical main steam export.+700 ℃≥ 25 MPa
9H276 WeldingWaste generation / biomass overheater+650 ℃≤ 25 MPa
10GH3030 / GH3044Super-temperature flue gas / burner+1100 ℃Keep pressure down.
Protection tube materialTemperature measure limitCorrosivenessTypical applications
316L+650 ℃WeakFrozen / Air / Water
Technical parameter table · Protect pipe material / temperature measurement capCross-reference
Protection tube materialTemperature measure limitCorrosivenessTypical applications
1Cr18Ni9Ti (321)+650 ℃MediumHeats / Reheaters
310S (0Cr25Ni20)+1100 ℃MediumFrozen / High Temperature Segment
Inconel 600+1100 ℃StrongMain steam / HTVP
H276+1100 ℃ExtremeWaste generation / high-corrosive flue gas
GH3030+1100 ℃StrongSuper-temperature flue gas / burner
GH3044+1200 ℃StrongSuper-temperature flue gas / burner
Ceramic (Al2O3 / SiC)+1700 ℃ExtremeBurner / Glass industry
Technical parameter table · Point type / Typical workCross-reference
Point TypeTypical Work StatusRecommended ModelHeat tube/outside
Overheated vapour 600 °C / 25 MPaExport of the heater / main steamWRNK-Inconel Whole exercise - 25-ANSI 2,500#-L1000-HartWhole exercise + Inconel 600 welds
Reheated steam 540 °C / 4~6 MPaReheaters are imported and exported.WRNK - Gradual - Inconel 600- ⁇ 20-Hg/T PN16-L600Gradual + Inconel 600
High pressure for water 290 °C / 25 MPaWater Operator / Save Coal AccessWRNK - Gradual -1 Cr18Ni9Ti- ⁇ 20 - HG/T PN25-L500Gradual + 1Cr18Ni9Ti
Screen overheater 450~580 °C / 15 MPaScreen OverheaterWRNK - Gradual - Inconel 600- ⁇ 22-HG/T PN16-L800Gradual + Inconel 600
Pack temperature 360 °C / 18 MPaBagWRNK-Darling-1Cr18Ni9Ti- ⁇ 16-Welding-L300Straight tube + 1Cr18Ni9Ti
Air preheater 30~200 °C / 0.1 MPaAir heaterWRNK - Direct-Kyper 316L- ⁇ 16-Franc-L3 00Straight line + 316L
Frozen temperature 800 ~ 1100 °C/ 0.1 MPaSave coals before/ preheater/ ovenWRNK - Straight-H3030-GH20 - Frank - L500Straight line + GH3030
After cooling water spray 400~540 °C / 15 MPaTemperature after cooling the sprayWRNK - Gradual - Inconel 600- ⁇ 22-Hg/T PN16-L600Gradual + Inconel 600
Supercritical main steam 600~630 °C / 25 MPaSupercritical, super-critical, main steam.WRNN - Whole exercise - F91+Inconel - ⁇ 25-ANSI 2500#-L1000-HartWhole exercise +F91 + stacks of Inconel + N
Nuclear power one-way coolant 320 °C / 15 MPaThe reactor coolant.WRNK - Direct pipe -1 Cr18Ni9Ti- ⁇ 20 - Welding - L500- Nuclear LevelDirect tube + 1Cr18Ni9Ti +Check Level Certification
Flame of the burner 1100 ~ 1700 °CFire zone of the furnaceWRPB - High temperature tolerance - ceramic protection tube - 25-Franc - L800High temperature resistant + ceramic protection tube + B-precious metal
Waste generation overheat steam 450 °C / 4 MPaWaste generation overheaterWRNK - Gradual - Hae-Hah, C-276 - ⁇ 20-Hg/T PN16-L800Gradual + Haps C-276 Welding
Technical parameter table · Point type / Typical workCross-reference
Point TypeTypical Work StatusRecommended ModelHeat tube/outside
- The temperature of the engine tank is 350 °C.Autobustrunk / Medium CylinderWRNK-Darling-1Cr18Ni9Ti- ⁇ 10-Snack-L200Straight tube + 1Cr18Ni9Ti
Hot tubing formTypical Work StatusNominal pressureRemarks
Straight lineLow pressure steam / water / water back / smoke≤ 2.5 MPaEconomic programme
Gradual expansion (stepping)Medium-high pressure overheat / reheater4~25 MPaMainstream power plant programme
Whole exercise.Supercritical main steam / HPX exit≥ 25 MPaHigh intensity, long life
WeldingHeat peroxide / flue gas corrosive process4~25 MPaCarbon steel matrix + Inconel / Harsh welding
Welding / screwdriverSave coal / Water / Press steam≤ 10 MPaSimple structure, easy maintenance
Sensor typeTemperature rangeSuitable operating conditionsSuggested Places
K40~+1300 ℃Main steam/ heater/ reheater/ smokePower station preferences, mainstream programmes
N40~+1300 ℃K Upgrade / Long-term stability of high temperaturesSupercritical / K drifting scene
E40~+900 ℃Medium-temperature vapour / WaterMedium-temperature, high heat.
J40~+750 ℃Media neutral / Revert atmosphereVacuum furnace / Retrogressive atmosphere
T40~+350 ℃Temperature / Cold End CompensationThe cold end compensation guide is special.
S0~+1600 ℃Precious Metal / High Temperature / StandardBurner / Standard Thermal Puppet
R0~+1600 ℃Precious metal/ similar to SBurner / Standard Thermal Puppet
B0~+1700 ℃Super-high / glass industryBurner / Super-heat
ConnectionApply sceneSpecificationsPressure rating
-Frank high.Heat perheater / reheater / main steamHG/T 20615 PN16~PN32 / ANSI 600#~2500#≤ 32 MPa
WeldingHeat persimulators / Save coal / Give the pipe wallsDirect pairing + Inconel≤ 25 MPa
ThreadWater / SteamNPT1/2 / G1/2 / M27×2≤ 10 MPa
CardAdjust depth / test loops for insertionNPT1/2 + Carat≤ 1.0 MPa
Activity FrankFrequently adjust depth of insertionDN25~50 + Bar≤ 1.6 MPa
Technical Parameter Table · Output Method / Applies sceneCross-reference
Output MethodApply sceneSupporting instrument
mV Direct OutputShort distance, performance testNumeric / DCS mV card
4-20 MA Two-line SystemMainstream power station siteDCS / DAH / Coordinated Control
4-20 mA + HartRemote grouping, parameterizationHart Handheld / 475 Comms
MODBUS RTUMultiple instrument network / RS-485PLC / Industrial gateway
PROFIBUS-PAIntegrated plant integrationDCS / Asset Management System
Technical parameter table · Step / ConsiderationsCross-reference
StepsConsiderationsDecision points
①Point media (vapour / water / smoke / air)Chapter 5 identifies the type of spot and typical work
②Media Temperature / Pressure / Flow Speed6.2 / 6.3 Table identifies the fraction number + thermal tube / the protective tube material
③Media vibration properties (combustion pulse / vortex vibration)High vibration, tweak, build / whole + spring support
④Insert Depth and Install SpacePipe 1/3 diameter + Install Space Limit ⁇ Select L and heat tube forms
⑤Medium corrosive (smoke containing S / Cl)Frozen gas corrosive C-276 stacks / Inconel 600 / GH3030
⑥Process Connection (Franc/ Welding / Thread)HG/T 20615 PN 16 ~ PN 32 / ANSI 600 # ~ 2500#
⑦Cold end compensation and compensation guideMainstream KX compensatory conduits; smart transporter interior compensation
⑧Output signal (4-20 maA / Hart / bus)mainstream Hart; performance test mV direct
⑨Protection level / Wirebox / DetonationIP65 Start; Wet Environment IP67/IP68; Explosive Exd/ Exia
⑩Increased strength accounting / Vibration accounting / drifting estimateAccounting for inherent frequencies by ASME PTC 19.3; long-term K-type high temperature consideration gamma variance
ComparativeThermal dolls for temperature measurement at the stationThermal resistance for temperature measurement at stations
Temperature measurement principleThermal power effects of SebekPlatinum resist temperature - electrical resistor linearity
Temperature measure limitType K 1300 °C/ S/R 1600 °C/ Type B 1700 °C+650 ℃ (protective tube) / +700 ℃ (hot kit)
Temperature below limit40 °C (type K/N/E/J/T); S/R/B 0 °C200 ℃(Pt100)
Accuracy classK/N ± 1.5 °C or ± 0.4% t; S/R ± 1.0 °C or ± 0.4% tPt100 Class A ±0.15 ℃ + 0.002 ⁇ t ⁇
Response timeNaked < 1 s; protective tube 8~20 s⁇ 25 About 30~60 s (two-layer structure)
Cold junction compensationNeed to compensate the guide + smart compensationNo, no, no. The wire blocker is covered.
Apply the pointMain vapour / Reheater / Fung/ Burner / Super-Hymonic MeasureThermost/ Reheater / Water / Medium-Leating Measure
Technical parameter table · Contrast / Thermal dolls for temperature measurement at power stationsCross-reference
ComparativeThermal dolls for temperature measurement at the stationThermal resistance for temperature measurement at stations
Long-term stabilityK gamma Divisive Risk, to be verified with major overhaul≤ 0.05 ℃, long-term stability.
Anti-interferenceWeak (mV signal vulnerable to interference, needs shield + ground)Medium (Telephones Counteracting Interference)
PriceMedium (S/R/B precious metal wires are more expensive)Medium (Pt100 peseta)
Typical applicationsMain steam export/ reheater/ flue gas/ burnerHigh pressure water/ saver / air heater
Technical parameter table · Periodic / Maintenance contentCross-reference
CycleMaintain ContentCriteria for judgement
Each shiftInspection: indicate temperature, record curve, alarm checkA deviation from historical values ⁇ ±2 ℃
MonthlyThe wire box is sealed, waterproof, ground-checked.No water, no no movement.
QuarterlyInsulation resistance test (500 V mega-e Table)Temperature. ≥ 1000 M once m
BiannualProtection of the appearance of the tube, wall thickness, welding and external examinationNo visible corrosive / crack / perforation
Every time I'm done with it,Heat tube appearance, wall thickness measurement, vibration accounting recalculation, heat electrical verification or replacementWall thickness is down. < 1.5 mm ;vibration accounting passes;K type ⁇ ±2.5 ℃ or ±0.75% t
Life expectancy by life expectancyReplacement of protective tube or whole unit dueBy 3-6 years of life