Single-crystal silica differential transmitterClick on the picture to zoom in.

PRODUCT SPECIFICATIONS

PRETRAN-SIL-150

Single-crystal silica differential transmitter

Monocrystalline silicon differential pressure transmitter with ±0.075%, ±0.1%, or ±0.2% accuracy options.

01

Classification: Single-crystal silica differential transmitter

02

Check configuration based on field work

⁇ Return single-crystalline variance transmitter classification

TECHNICAL SPECIFICATIONS

Technical specifications

PRETRAN-SIL-150

Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.

View selection tables ↓
ModelPRETRAN-SIL-150
Measurement principleMonocrystalline silicon piezoresistive or resonant differential pressure sensor with digital signal processing
Measurement typeDifferential pressure (D) / flow with an orifice plate (Q) / level (L)
Measurement rangeRanges from 0–100 Pa to 0–6 MPa; adjustable 100:1 turndown
Accuracy class±0.075% / ±0.1% / ±0.2% (Optional)
Maximum static pressure10MPa / 25MPa (Optional)
Overload capacityOne-way static pressure protection: 14 MPa in the forward direction for the 25 MPa static pressure version
Output signal4–20mA (DC) + HART / RS485 (MODBUS) Optional
Power supply12–36VDC (standard 24VDC)
Load capacity(Supply voltage − 12 V) / 0.02 A, up to 1.2 kΩ
Sensor capsuleMonocrystalline silicon sensor with 316L isolation diaphragm (optional Hastelloy C276 or tantalum)
ConstructionDirect-mount three-valve manifold or dual remote seals (1–15 m capillaries)
Process connection1/2NPT (F) three-valve manifold interface / DN50–DN80 flange (PN1.0–4.0)
Display type5-digit local LCD showing percentage or engineering units, with rotatable display and magnetic adjustment through the cover
Damping time0–32s Configurable
Stability±0.1% per year, with an optional five-year calibration interval
Process medium temperature-40–+120℃ (dual remote seals to +350℃)
Ambient temperature-40~+85℃
Temperature compensationDigital temperature compensation throughout the −10 to +60 °C range
Ingress and explosion protectionIP66/IP67; Ex d II C T6 Gb / Ex ia II C T4 Ga (Optional)
Fill fluidSilicone oil (standard) / low-temperature silicone oil / food-grade glycerin
Applicable standardsGB/T 17614 / IEC 61010 / HART 7 / SIL2 (hardware redundancy Optional)
Suitable mediaGas, liquid, steam differential pressure / flow/ level measurement, high accuracy measurement application (compatible 316L)

Product selection

PRETRAN-SIL-150
Construction
CodeConstruction
S1Three-valve manifold straight chain (Standard)
S2Double flat Flange long-distance
S3Double-plug Flange long-distance (high temperature/slurry)
Range options (kPa)
CodeRange options (kPa)
R10–100Pa–0–1kPa (micro Differential pressure)
R20~1kPa~0~10kPa
R30~10kPa~0~100kPa
R40~100kPa~0~6000kPa(6MPa)
Accuracy class
CodeAccuracy class
E1±0.2%
E2±0.1%
E3±0.075%
Maximum static pressure
CodeMaximum static pressure
P110MPa
P225MPa
Output signal
CodeOutput signal
O14~20mA + HART
O24~20mA + RS485(MODBUS-RTU)
Isolation diaphragm / flange materials
CodeIsolation diaphragm / flange materials
M1316L Stainless steel
M2Hastelloy C276
M3Tantalum Ta (strong corrosive)
Capillary length (remote seal)
CodeCapillary length (remote seal)
C1Straight chain (no Capillary)
C22m (Standard)
C35m
C410m / 15m (Specify when ordering)
Display and adjustment
CodeDisplay and adjustment
L1No display (Standard header)
L25 LCD Display
L3LCD + Magnetic pens are off the grid.
Explosion protection marking
CodeExplosion protection marking
X1Non-Ex
X2Flameproof Ex d II C T6 Gb
X3Intrinsically safe Ex ia II C T4 Ga

Confirm specifications and ordering options

Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.

Contact us
PRETRAN-SIL-150 Monocrystalline Silicon Differential Pressure Transmitter