12V/45mA driver, switch output separation fenceClick on the picture to zoom in.
PRODUCT SPECIFICATIONS
VISCON-ISO-250
12V/45mA driver, switch output separation fence
12V/45mA driver, switch output fence, 12V/45mA switch output fence
01
Classification: 12V/45mA driver, switch output fence
02
Check configuration based on field work
TECHNICAL SPECIFICATIONS
Technical specifications
Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.
View selection tables ↓| Model | VISCON-ISO-250 |
|---|---|
| Product function | Take it. safe area Switches to the control system (relays contact points, transistor-collector circuits, logical level) signal passage intrinsic safety isolation After, by 12VDC / 45mA It's... Intrinsically safe Power Drive Hazardous area Electromagnetic valves, sound light. Alarm Switch loads such as switches, small relays, etc. |
| Explosion protection type | Intrinsic safety Type-associated equipment [T] Ex ia] II C;outside accessable 0 Region, 1 Region, 2 Sector II A/II B/II C Type of environment Intrinsically safe type Switch Load |
| Channel configuration | Standard one input, one output (1 Channels; optional two inputs, two outputs (2 Independent separation of passages; Optional One input, two outputs (Same signal drive two-way loads) |
| Input signal | Dry contact (voltage-free contact), wet contact (DC 24V, input current ≤5mA), transistor central pole opening (NPN/PNP optional), logical level (0–5V/0–24V); input and output electrical separation |
| Input threshold | High level ≥4.5V (or touch closed), low level ≤1.5V (or touch disconnected); input current ≤5mA; with a shake-proof filter (available 0–5s) |
| Output drive | Intrinsically safe type switch output, 12VDC / 45mA (gap); direct driver intrinsically safe electromagnetic valve, acoustic alarm device, intrinsically safe relay wire; output source type (sourcing) driven |
| Output protection | Output short-circuit (≤55mA) and passover protection; Reverse polarity protection; sensory load belt renewal diode (inline) |
| Response time | ≤10ms (Input change to output set); with programmable delay 0–5s (for time series of lock actions) |
| Isolation performance | Three-way isolation between input, output, and power. Isolation: 1500 V AC for 1 min. Insulation resistance: ≥100 MΩ at 500 V DC. Common-mode rejection: ≥120 dB. |
| Intrinsic safety parameters | Um=250VAC/DC; Uo=15.4V, Io=52mA, Po=0.20W; Co=2.4μF, Lo=2.0mH (II C); II B Environment Co=10μF, Lo=8.0mH |
| Output indicator | Panel LED channel-by-channel indicator output status (conductor/disconnect) for lockback circuit failure determination |
| Power supply | DC 20–35V (Quota 24V); single channel power ≤0.8W, double channel ≤1.4W; with reverse Overvoltage protection |
| Mounting | Snap-on mounting to a standard 35 mm DIN rail. Width: 12.5 mm for one channel or 18 mm for two channels. |
| Wiring | Plugged screws (2.5mm2); Hazardous area ender blue identification |
| Operating environment | Temperature -20–+60℃, relative humidity ≤95%RH (Non-condensing) |
| Overall dimensions | Single channel 12.5 × 110 × 118mm; double channel 18 × 110 × 118mm |
| Instrument weight | About 0.12kg (single channel) |
| Applicable standards | GB 3836.1 / GB 3836.4 / GB 3836.15 (intrinsically safe system)/ GB/T 17626 (EMC)/ IEC 61000-6-2 |
| Certification requirements | Explosion protection certificate for access to national blast detection facilities; GB 3836.15 accounting Lo for driving sensor load matches the load perception |
| Typical applications | Switch output circuits for locking systems in chemical, petrochemical, oil and gas installations: hazardous area intrinsically safe electromagnetic valves, aerodynamic valve pioneer valves, acoustic alarm devices, blastproof relays; SIS/ESD separation of the system from the on-site execution element |
| Product features | 12V/45mA intrinsically safe drive, directly driving most intrinsically safe electromagnetic valves and acoustic devices to save intermediate relays; input compatibility dry contact / wet contact / transistor/logical level, compatible with various control systems; short-circuit limit protection to prevent intrinsically safe circuit from being ignited; panel LED visual Display action status, fast-tracking of chain failure sequences |
Product selection
VISCON-ISO-250| Code | Number of channels |
|---|---|
| C1 | One input, one output (1 channel) |
| C2 | Two inputs, two outputs (2 channel, stand alone) |
| C3 | One input, two outputs (1 signal drive 2 road load) |
| Code | Input type |
|---|---|
| I1 | Dry contact (Voltage-free contact) |
| I2 | Wet contact DC 24V |
| I3 | Transistor ICD open circuit (NPN) |
| I4 | Logical level 0–5V / 0–24V |
| Code | Output drive |
|---|---|
| O1 | 12VDC / 45mA (Standard) |
| O2 | 12VDC / 45mA source + short-circuit protection |
| O3 | 24VDC / 30mA (order) |
| Code | Switching action |
|---|---|
| F1 | Normally open (output with input guide) |
| F2 | Normally closed (reverse output) |
| F3 | Normally open / Normally closed programmable |
| Code | Delay and Filter |
|---|---|
| D1 | No delay (≤10ms response) |
| D2 | Enter tremors 0–5s available |
| D3 | D2 + output timed 0–5s available |
| Code | Explosion protection marking |
|---|---|
| E1 | [Ex ia] II C (Standard) |
| E2 | [Ex ia] II B |
| E3 | [Ex ib] II C |
| Code | Indication and diagnostics |
|---|---|
| L1 | No instructions |
| L2 | Channel-by-channel output LED indication (Standard) |
| L3 | L2 + output failure point |
| Code | Power supply |
|---|---|
| P1 | Independent 24VDC electricity supply |
| P2 | DIN rail bus power supply (power distribution module) |
| P3 | Redundant 24VDC double power supply |
Confirm specifications and ordering options
Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.
Contact us