Switch input, relay output fence-SA6120Click on the picture to zoom in.
PRODUCT SPECIFICATIONS
VISCON-ISO-300
Switch input, relay output fence-SA6120
Switch input, relay output fence-SA6120, switch input relay output barrier SA6120
01
Classification: Switch input, relay output fence-SA6120
02
Check configuration based on field work
TECHNICAL SPECIFICATIONS
Technical specifications
Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.
View selection tables ↓| Model | VISCON-ISO-300 (corresponding model SA6120) |
|---|---|
| Product function | Collecting hazardous area switch amount signals (voltage-free contact, NAMUR approach switch, wet contact), output in safe area after intrinsic safety isolation in relay contact point for DCS, PLC, lock system for state collection and Alarm |
| Explosion protection type | Intrinsic safety Type-associated equipment [T] Ex ia] II C;inputendable 0 Region, 1 Region, 2 Sector II A/II B/II C Switching sensors in explosive gas-type environments |
| Channel configuration | Standard two inputs, two outputs (2 channel is isolated and can be used in a single channel); 1 road switch + 1 group relay output (1 normally open + 1 Normally closed) |
| Input type | NAMUR Type approaching switch (conforms) IEC 60947-5-6, 8.2VDC Electricity distribution, voltage-free dry contact, wet contact (DC 24V); input impedance ≤1kΩ |
| Input characteristics | NAMUR Door limit: ≤1.2mA judgement (0), ≥2.1mA interpretation (1); dry contact query voltage 8.2V query current ≤8mA; wet contact input current ≤6mA |
| Input Frequency | ≤5kHz (square wave, space ratio 30%–70%); available for low speed Pulse count and turn switch collection |
| Output Type | Relay touchpoint output, 1 normally open + 1 normally closed (conversion contact SPDT); contact rating 250VAC / 2A, 30VDC / 2A (retardation load) |
| Output Logic | Normally open / normally closed programmable (both positive and counter-effects); output duration 0–10s; single steady state pulse widening 0.1–10s |
| Line Testing | Programmable circuit breaker and short circuit detection: input loop breaker or short circuit, output by default action and LED (NAMUR) |
| Isolation performance | Input-output-power-triple-end isolation; isolation voltage 1500VAC/1min; insulation resistance ≥100MΩ (500VDC) |
| Intrinsic safety parameters | Um=250VAC/DC; Uo=10.6V, Io=14mA, Po=37mW; Co=2.4μF, Lo=165mH (II C); II B Environment Co=10μF, Lo=1H |
| Response time | ≤10ms (Input change to relay action, excluding time extension) |
| Power supply | DC 20–35V (Quota 24V); single channel power ≤0.9W, double channel ≤1.5W; with reverse Overvoltage protection |
| Output indicator | Panel by channel LED: power, input status, relay action, circuit failure (four light indicator) |
| Mounting | 35mm standard DIN rail carcass; two-channel thickness 18mm, one-channel 12.5mm |
| Wiring | Plugged screws (2.5mm2); Hazardous area ender blue mark and set side by side with other circuits |
| Operating environment | Temperature -20–+60℃, relative humidity ≤95%RH (Non-condensing) |
| Overall dimensions | 18 × 110 × 118mm (two channels, wide × high × deep) |
| Instrument weight | 0.15kg |
| Applicable standards | GB 3836.1 / GB 3836.4 / GB 3836.15 (intrinsically safe system)/ GB/T 17626 (EMC)/ IEC 60947-5-6 (NAMUR) |
| Certification requirements | Explosion protection certificate; intrinsically safe circuit has to account for cable senses and capacitation by GB 3836.15 |
| Typical applications | Chemical, petrochemical, oil and gas installations, valve position feedback, level switch, button and alarm touchpoint status acquisition; with SIS/ESD, DCS digital input cards, separate Hazardous area and Safe area switches |
| Product features | NAMUR compatible with Dry contact / Wet contact, with access to all types of switches in the field; with circuit break-ups and short-circuit detection, distinguishing between normal disconnections and circuit failure; relay output that directly drives intermediate relays, indicator lights and Alarm; two channel thin structures with high inner density |
Product selection
VISCON-ISO-300| Code | Number of channels |
|---|---|
| C1 | One input, one output (1 channel) |
| C2 | Two inputs, two outputs (2 channel, Standard) |
| C3 | Four inputs, four outputs (4 channel, order) |
| Code | Input type |
|---|---|
| I1 | NAMUR approach switch (8.2V distribution) |
| I2 | Voltage-free dry contact |
| I3 | Wet contact DC 24V |
| I4 | NAMUR + dry contact + Wet contact compatibility (Standard) |
| Code | Output Type |
|---|---|
| O1 | 1 normally open + 1 normally closed (SPDT, Standard) |
| O2 | 2 normally open (NO) |
| O3 | Solid state relay output (no contact, order) |
| Code | Contact rating |
|---|---|
| K1 | 250VAC/2A, 30VDC/2A (Standard) |
| K2 | 250VAC/5A、30VDC/5A |
| K3 | 125VAC/0.5A (sign level, long life) |
| Code | Line Testing |
|---|---|
| D1 | No detection |
| D2 | Open-circuit detection |
| D3 | Breakline + short circuit test (standard, NAMUR) |
| Code | Action Features |
|---|---|
| F1 | Normally open (positive) |
| F2 | Normally closed (reactional) |
| F3 | Normally open / normally closed programmable + delay 0–10s |
| F4 | F3 + uniform Pulse extension |
| Code | Explosion protection marking |
|---|---|
| E1 | [Ex ia] II C (Standard) |
| E2 | [Ex ia] II B |
| E3 | [Ex ib] II C |
| Code | Power supply |
|---|---|
| P1 | Independent 24VDC electricity supply |
| P2 | DIN rail bus power supply (power distribution module) |
Confirm specifications and ordering options
Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.
Contact us