Handheld Smart OperatorClick on the picture to zoom in.

PRODUCT SPECIFICATIONS

VISCON-OP-100

Handheld Smart Operator

Handheld smart operator, handheld smart operator

01

Classification: Handheld smart operator

02

Check configuration based on field work

⁇ Return Handheld Smart Operator Classification

TECHNICAL SPECIFICATIONS

Technical specifications

VISCON-OP-100

Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.

View selection tables ↓
ModelVISCON-OP-100
Product functionOn site HART intelligence transmitter, valve positioner configuration, parameter reading and writing and circuit debugging; replace traditional hand-manufacturing, with 4–20mA return signal source and gauge, one device completes the entire process from delivery to failure screening
Communication protocolsHART 5 / 6 / 7 fully compatible, supporting point-to-point and point-to-point mode, sudden (Burst) mode; optional MODBUS RTU (RS485) main station function
Loop connectionA pair of 4mm banana plugs attached to 4–20mA return road at any location; inner 250Ω telecommunications electrical resistance (toggle) to communicate without external resistance
Display and controls3.5 inch 320×480 Colour touch screen + 5-way navigation key + 3 functionality keys; readable under sunlight, automatically adjusted with back light
Configuration parametersBits, units of measurement, range high and low limits, damping time, output method (linear/open), sensor fine-tuning (Trim), zero shift, 4mA/20mA electrical current calibration, circuit back test (Loop Test)
Command supportHART General Command, typical Command, Device Community Command; optional Mainstream brand equipment description (DD) library to menu Configuration; support devices to read from diagnostic information
Signal source functionOutput-fixed 4mA / 12mA / 20mA and 0–25mA Any value (to be external) loop power, or use built-in loop power supply) for verification DCS Enter card and Valve positioner
Measurement functionDirect current 0–25mA (±0.05%RD), direct current voltage 0–30V; can Display % of current corresponding to project value
Data managementInternal 8GB Storage, Saveable 1000 Equipment Configuration Quickshot and measurement records; support bet-in search, Configuration Match with one keyback
Power supply and battery lifeLithium ion batteries 3.7V / 3000mAh, continuous use ≥12h; USB Type-C recharge to support mobile power recharge
Data ExportUSB Type-C connects to the top machine, export configuration files (txt/csv) and measurement records; optional bluetooth or WiFi wireless transmission to mobile phone APP
Protection and environmentIngress protection IP54 (optional IP65); working temperature -10–+50℃; storage temperature -20–+60℃
Overall dimensions180 × 85 × 35mm (without pens and condoms)
Instrument weightAbout 0.35kg (including batteries)
Additional ConfigurationInline LED lighting for nighttime or in-box operations; laced with gator clips and attached to end rows
Applicable standardsHART communication protocols Normative HCF_SPEC-13 / GB/T 17626 (EMC) / Reference JJG 882 (pressure Transmitter Verification regulation)
Typical applicationsReturn check range before the new device is shipped; calibration transmitter Zero and range during the overhaul; failure check will determine whether the on-site instrument, line or DCS card problem
Product featuresInline 250Ω telecommunications electrical resistance, no more wire-to-wire to access circuits on site; colour-screen touch-and-physical-key operations, and gloves can also turn over menus; Configuration snapshots to save and match, retrofitted and resonance of parameters; and a combination of signal sources and current meters to reduce the number of accompanying tools

Product selection

VISCON-OP-100
Communication protocols
CodeCommunication protocols
H1HART 5/6/7 (Standard)
H2HART 5/6/7 + MODBUS RTU(RS485)
H3HART + Foundation on-site bus (order)
Display and controls
CodeDisplay and controls
D13.5 inch colour screen + touch (Standard)
D22.8 inch single screen + button (Economy type)
D3Colourscreen touch + entity navigation key double operation
Device library configuration
CodeDevice library configuration
L1General Command (HART general/ Typical)
L2Generic + Typical (Standard)
L3Mainstream brand DD library (menu Configuration)
L4L3 + supports import custom DD
Loop power
CodeLoop power
P1Getting electricity back on the road. No external power supply.
P2Internal 24V Loop power supply (separable table)
P3External 24V power adapter
Storage capacity
CodeStorage capacity
M18GB (Standard)
M232GB
Data interface
CodeData interface
X1USB Type-C
X2USB Type-C + Bluetooth 5.0
X3USB Type-C + Bluetooth + WiFi
Ingress protection
CodeIngress protection
E1IP54 (Standard)
E2IP65
E3IP65 + intrinsically safe Ex ia II C T4 (Enable Hazardous area)
Accessory configuration
CodeAccessory configuration
A1Standard (Counter + leather + data lines)
A2Add 250Ω switchbox tied to the ender
A3Portable printing module (on-site logs)

Confirm specifications and ordering options

Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.

Contact us