Handheld Smart OperatorClick on the picture to zoom in.
PRODUCT SPECIFICATIONS
VISCON-OP-100
Handheld Smart Operator
Handheld smart operator, handheld smart operator
01
Classification: Handheld smart operator
02
Check configuration based on field work
TECHNICAL SPECIFICATIONS
Technical specifications
Check the specifications against your operating conditions and use the selection tables to confirm your order configuration.
View selection tables ↓| Model | VISCON-OP-100 |
|---|---|
| Product function | On site HART intelligence transmitter, valve positioner configuration, parameter reading and writing and circuit debugging; replace traditional hand-manufacturing, with 4–20mA return signal source and gauge, one device completes the entire process from delivery to failure screening |
| Communication protocols | HART 5 / 6 / 7 fully compatible, supporting point-to-point and point-to-point mode, sudden (Burst) mode; optional MODBUS RTU (RS485) main station function |
| Loop connection | A pair of 4mm banana plugs attached to 4–20mA return road at any location; inner 250Ω telecommunications electrical resistance (toggle) to communicate without external resistance |
| Display and controls | 3.5 inch 320×480 Colour touch screen + 5-way navigation key + 3 functionality keys; readable under sunlight, automatically adjusted with back light |
| Configuration parameters | Bits, units of measurement, range high and low limits, damping time, output method (linear/open), sensor fine-tuning (Trim), zero shift, 4mA/20mA electrical current calibration, circuit back test (Loop Test) |
| Command support | HART General Command, typical Command, Device Community Command; optional Mainstream brand equipment description (DD) library to menu Configuration; support devices to read from diagnostic information |
| Signal source function | Output-fixed 4mA / 12mA / 20mA and 0–25mA Any value (to be external) loop power, or use built-in loop power supply) for verification DCS Enter card and Valve positioner |
| Measurement function | Direct current 0–25mA (±0.05%RD), direct current voltage 0–30V; can Display % of current corresponding to project value |
| Data management | Internal 8GB Storage, Saveable 1000 Equipment Configuration Quickshot and measurement records; support bet-in search, Configuration Match with one keyback |
| Power supply and battery life | Lithium ion batteries 3.7V / 3000mAh, continuous use ≥12h; USB Type-C recharge to support mobile power recharge |
| Data Export | USB Type-C connects to the top machine, export configuration files (txt/csv) and measurement records; optional bluetooth or WiFi wireless transmission to mobile phone APP |
| Protection and environment | Ingress protection IP54 (optional IP65); working temperature -10–+50℃; storage temperature -20–+60℃ |
| Overall dimensions | 180 × 85 × 35mm (without pens and condoms) |
| Instrument weight | About 0.35kg (including batteries) |
| Additional Configuration | Inline LED lighting for nighttime or in-box operations; laced with gator clips and attached to end rows |
| Applicable standards | HART communication protocols Normative HCF_SPEC-13 / GB/T 17626 (EMC) / Reference JJG 882 (pressure Transmitter Verification regulation) |
| Typical applications | Return check range before the new device is shipped; calibration transmitter Zero and range during the overhaul; failure check will determine whether the on-site instrument, line or DCS card problem |
| Product features | Inline 250Ω telecommunications electrical resistance, no more wire-to-wire to access circuits on site; colour-screen touch-and-physical-key operations, and gloves can also turn over menus; Configuration snapshots to save and match, retrofitted and resonance of parameters; and a combination of signal sources and current meters to reduce the number of accompanying tools |
Product selection
VISCON-OP-100| Code | Communication protocols |
|---|---|
| H1 | HART 5/6/7 (Standard) |
| H2 | HART 5/6/7 + MODBUS RTU(RS485) |
| H3 | HART + Foundation on-site bus (order) |
| Code | Display and controls |
|---|---|
| D1 | 3.5 inch colour screen + touch (Standard) |
| D2 | 2.8 inch single screen + button (Economy type) |
| D3 | Colourscreen touch + entity navigation key double operation |
| Code | Device library configuration |
|---|---|
| L1 | General Command (HART general/ Typical) |
| L2 | Generic + Typical (Standard) |
| L3 | Mainstream brand DD library (menu Configuration) |
| L4 | L3 + supports import custom DD |
| Code | Loop power |
|---|---|
| P1 | Getting electricity back on the road. No external power supply. |
| P2 | Internal 24V Loop power supply (separable table) |
| P3 | External 24V power adapter |
| Code | Storage capacity |
|---|---|
| M1 | 8GB (Standard) |
| M2 | 32GB |
| Code | Data interface |
|---|---|
| X1 | USB Type-C |
| X2 | USB Type-C + Bluetooth 5.0 |
| X3 | USB Type-C + Bluetooth + WiFi |
| Code | Ingress protection |
|---|---|
| E1 | IP54 (Standard) |
| E2 | IP65 |
| E3 | IP65 + intrinsically safe Ex ia II C T4 (Enable Hazardous area) |
| Code | Accessory configuration |
|---|---|
| A1 | Standard (Counter + leather + data lines) |
| A2 | Add 250Ω switchbox tied to the ender |
| A3 | Portable printing module (on-site logs) |
Confirm specifications and ordering options
Contact us with the measurement target, operating conditions, and installation requirements to confirm your configuration.
Contact us